Goodman AC & Heat Pump Error Codes: Full List & Meanings

Every Goodman ac & heat pump error code in the Goodman GSXC7 installation instructions, unitary diagnostic codes, as published by Alpine Home Air (manual copy), with its meaning. This list covers gsxc7 variable-speed air conditioners (7-segment diagnostic display). Codes vary by model, so confirm in your owner's manual. Support: Goodman dealer or Goodman customer support (goodmanmfg.com).

Codes by system

Venting / airflow

Power supply

All Goodman ac & heat pump error codes

Codes marked "Reset only" or "Service" have no separate page because the manufacturer publishes no owner fix beyond a reset or a service call.

CodeMeaningSystemOwner action
A2Outdoor air temperature sensor fault: the sensor is shorted, open, disconnected or out of range.SensorsService
A3Outdoor coil temperature sensor fault: the sensor is shorted, open, disconnected or out of range. A heat pump may fail to heat.SensorsService
E5Open fuse: a short in the low-voltage wiring has blown the control's fuse, and the system fails to operate.Power supplyService
EEInternal fault: board mis-operation; the manual lists welded compressor relay contacts as the cause.Control / electronicsService
b0The indoor circulator blower motor is not running when it should be (communicating ComfortBridge systems).Motor / driveService
b9Low indoor airflow: airflow is lower than demanded, so the system runs at reduced performance or stays on low stage. Listed causes include an indoor blower problem, blocked filters, restrictive or undersized ductwork, or mismatched indoor and outdoor units.Venting / airflowOwner checks
d0Data not yet on the communicating network (ComfortBridge).Control / electronicsService
d1Invalid data on the communicating network.Control / electronicsService
d2System mismatch: the outdoor unit requires more airflow than the indoor unit can deliver, or shared data is incompatible or missing.Control / electronicsService
d3Configuration error with the shared data sent to the control.Control / electronicsService
d4Invalid memory card data.Control / electronicsService
01Low side fault or low pressure switch open. Listed causes: low refrigerant charge, a liquid-line restriction, an indoor blower motor failure or the thermostat set extremely low. Shown as L1 when the control locks out. Also: L1HeatingService
02High side fault or high pressure switch open. Listed causes: a blocked condenser (outdoor) coil or the outdoor fan not running. Shown as L2 when the control locks out. Also: L2Venting / airflowOwner checks
03Short cycling: run time for the last four cycles was too short. Listed causes: intermittent thermostat demand or a faulty compressor relay.Control / electronicsService
04Locked rotor: the compressor did not start. Listed causes: seized compressor bearings, a failed run capacitor or its wiring, or low line voltage.Motor / driveService
05Open circuit: power is disconnected, the compressor protector has failed, or the compressor is not wired properly to the control.Power supplyOwner checks
06Open start circuit: the compressor start winding is open, the run capacitor or its wiring has failed, or the compressor is miswired. Shown as L6 when locked out. Also: L6Motor / driveService
07Open run circuit in the compressor. Shown as L7 when locked out. Also: L7Motor / driveService
L8Low line voltage: the control detects supply voltage below the rating-plate range.Power supplyOwner checks
H8High line voltage: the control detects supply voltage above the rating-plate range.Power supplyService