GE GeoSpring water heater Error Codes: Full List & Meanings

Every GE GeoSpring water heater error code in the GE GeoSpring water heater error-code chart, as published by Sears PartsDirect, with its meaning. Codes vary by model, so confirm in your owner's manual. Support: GE Appliances support (products.geappliances.com).

Smell gas? Leave the building now. Do not touch light switches, phones or appliances inside. Call your gas utility or 911 from outside. CO alarm sounding or headache, dizziness or nausea? Get everyone outside and call 911. Gas valves, burners, venting and wiring are for a licensed technician only. See our safety policy.

Codes by system

Heating

All GE GeoSpring water heater error codes

Codes marked "Reset only" or "Service" have no separate page because the manufacturer publishes no owner fix beyond a reset or a service call.

CodeMeaningSystemOwner action
FACompressor discharge temperature not rising. The T4 sensor (compressor outlet temperature sensor) must detect at least a 20-degree temperature rise during the first 30 minutes of run time.HeatingService
FBCompressor discharge temperature not stable. The T4 sensor (compressor outlet temperature) must be greater than 120 degrees Fahrenheit after 30 minutes of run time.HeatingService
FCEvaporator frosted over. The T3a sensor (evaporator inlet temperature) must be greater than 20 degrees Fahrenheit after 30 minutes of run time. The T3 sensor should measure approximately 10k ohms at 77 degrees or 57k-3k when the evaporator inlet temperature is 15-130 degrees.HeatingService
FDSuper heat is too low.HeatingOwner checks
FEDischarge temperature above the limit. The compressor discharge temperature exceeded 240 degrees Fahrenheit.HeatingService
F2Tank temperature sensor failure. The control checks the T2 tank sensor temperature before the compressor starts and it must be 30-u2013170 degrees Fahrenheit. The ohm resistance should measure approximately 10k ohms at 77 degrees.HeatingService
F3Compressor failure. The control energized the compressor but the current sensor does not detect any current flow.HeatingService
F4Fan failure.Venting / airflowService
F5T3a sensor failure. The ohm resistance of the T3a, T3b and T5 sensors should measure approximately 10k ohms at 77 degrees.SensorsService
F6T3b sensor failure. The ohm resistance of sensors T3a, T3b and T5 must measure approximately 10k ohms at 77 degrees Fahrenheit.SensorsService
F7T4 sensor failure. The ohm resistance of T4 sensor should measure approximately 55k ohms at 77 degrees Fahrenheit.SensorsService
F8T5 sensor failure. The ohm resistance should measure approximately 10k ohms at 77 degrees Fahrenheit.SensorsService
F9Lower heating element failure. The heating element should measures 12.8-18.75 ohms of resistance.HeatingService
F10Upper heating element failure. The heating element should measure 12.8-18.75 ohms of resistance.HeatingService